0 - 14 pH pH ±2500 mV ORP 0.054 - 20 /200 /2000 /20000 /200000 μS Conductivity 0 - 20 ppm or mg/l • 0-200% SAT Dissolved Oxygen Configuration Outputs All outputs Relay, SSR and Output mA are configurable with primary and secondary measure. Current outputs 4 - 20mA Galvanic isolation . Two independent programmable Output Measures with Proportional routine regulation. Relay Outputs Two independent relays, two set points, alarm remote and back washing probe setting by software. On/OFF, Timed routine function setting. Solid State Relay (SSR) Two Frequency output signal, two set points with Proportional routine regulation. Graphic display 128 x 128 pixel resolution monochrome display with graphic icons to show digital output status, washing cycle, alarms menu. Enclosure box wall mounting ABS plastic material IP65 (144x144) and panel mounting IP54 (96x96) Universal Power Supply 100 - 240 Vac 50/60 Hz 0 - 99999 l/sec Flow Rate 0 - 0.5 / 1/ 2/ 5/ 10/ 20/ 200 ppm Chlorine and Chlorine Dioxide 0 - 500/ 1000/ 2000/ 10000/ 100000 ppm Hydrogen Peroxide 0 - 0.5/ 2/ 5/ 10 ppm Ozone (03) 0 - 500/ 2000/ 10000/ 20000 ppm Peracetic Acid 0 - 1/ 10/ 100 NTU/FTU Turbidity with PT100/PT1000 32 - 212 °F (0 - 100°C) Temperature Multi-Color Backlight Function Four different Backlight colors to underline functions. • Waste Water • Drinking Water • Pure Water • Cooling Towers • Boiler • Reverse Osmosis • Crate Wash • Galvanic Process • CIP • Irrigation • Swimming Pool • Dairy Applications Measurement range The Kontrol 100-series are advanced controllers designed for simpler high-end applications.The units feature an independent proportional control output, probe quality checking and a variety of outputs . The user has full programming authority. Kontrol 100 Single-parameter controller 17 Controllers & Sensors